EMERSON Product|English

BM5 Series slam-shut valve Tartarini™

BM5 Series slam-shut valve Tartarini™

BM5 Series slam-shut valve is an automatic shutoff appliance suitable for installation as a safety device in regulating stations and gas distribution piping. BM5 Series slam-shut valve is used in natural gas, air, propane, butane, LPG, city gas, nitrogen, carbon dioxide, hydrogen regulating or distribution installations.The slam-shut valve is designed to shutoff the flow of gas in the event of the pressure rising above or falling below the predefined levels.

Body Sizes

DN 25, 40, 50, 65, 80, 100, and 150 / NPS 1, 1-1/2, 2, 2-1/2, 3, 4, and 6

End Connection Style

PN 16, 16 EN 25 / CL150, CL300, and CL600

Maximum Inlet Pressure

100 bar / 1450 psig

Overpressure Set Range

0,03 to 80 bar / 0.44 to 1160 psig

Underpressure Set Range

0,01 to 80 bar / 0.15 to 1160 psig

Accuracy Class

Up to ± 1%

Response Time

< 1 second

Temperature Capabilities

Standard Temperature version: Working: -10° to 60°C / 14° to 140°F Low-Temperature version:Working: -20° to 60°C / -4° to 140°F

Axial Flow

Sleeve Valve

Protected Seal Pad

Push-Button Manual Emergency Release

Manual Reset through Rotation of the Reset Shaft Only